Key Considerations Before Installation
Before diving into the installation, ensure you check the date codes for your controllers. Models prior to 2604 for unitary controllers and 2606 for VAV controllers will require the engineering kit.
Setting up your Ethernet connection is also vital.
Insure your IPv4 address is correctly configured to:
- 169.254.43.211
- Subnet of 255.255.0.0
- Gateway of 169.254.43.1
The Installation Process
These contain the necessary jar files and firmware for the upgrade. Make sure you have these ready.
You’ll need two essential folders:
- IRM Tool software
- IRM Tool
Installation
Once everything is set
Open your Honeywell Workbench
Two main applications used
Global FCU & Global VAV
Teaching the controller,
Right-click and select Teach to Controller
Final Steps and Confirmation
After ensuring everything is in order, attempt a full teach again. ]
Once successful, you can generate the wizard configuration:
- successful installation is confirmed when the ring light on your VAV controller turns solid green, indicating it’s ready to go.
- This process mirrors the steps taken for unitary controllers, making it straightforward once you've mastered the VAV setup.